FICHA TÉCNICA PARA CABLE DE ENERGÍA 0.6 / 1kV 4C 50 SQmm
NO. | ITEM | UNIT | DATA |
1 | Name of Manufacturer: | Beijing Huayuan Gaoke | |
Cable Co.,Ltd. | |||
1.2 | Country of Manufacturer: | China | |
2 | Which type of manufacturing process viz. Continuous Catanery Vulcanisation (CCV) or vertical Catanery Vulcanisation system (VCV) or horizontal MDCV will be used to ensure circularity and concentricity of the extruded layers around the conductor. | CCV | |
3 | Type of Cable: | Cu/XLPE /PVC | |
4 | Rated nominal voltage | kV | 0.6/1 |
5 | Rated Maximum voltage | kV | 1.2 |
6 | Nominal cross-sectional area of Conductor | Sq.mm | 50 |
7 | Conductor | ||
7.1 | Material | Copper | |
7.2 | Shape & formation | Round | |
7.3 | Diameter of conductor | mm | 8.3 |
7.4 | Dia.Of Single Wire/Number of strands | mm | 2.98/7 |
8 | Insulation | ||
8.1 | Material | XLPE | |
8.2 | Insulation Thickness(Min.Avg.) | mm | 1 |
8.3 | Diameter of Insulation(Approx.) | mm | 10.3 |
9 | Filler | ||
9.1 | Material | Non-hygroscopic Filler | |
9.2 | Diameter of Laid-Up Core | 24.9 | |
10 | Bedding tape | ||
10.1 | Material | Nonwoven tape | |
10.2 | Approximate thickness | mm | 0.2 |
10.3 | Diameter over of bedding (Approx.) | mm | 25.7 |
11 | Outer Sheath | ||
11.1 | Material | PVC | |
11.2 | Outer Sheath Thickness(Nominal) | 1.9 | |
11.3 | Over Diameter(Approx.) | 29.5 | |
12 | Conductor Weight | kg/km | 1657 |
12.1 | Total Cable Weight (Approx.) | kg/km | 2123 |
13 | Minimum Bending Radius | ||
13.1 | During Installation | mm | 1200 |
13.2 | Installed | mm | 1000 |
14 | Maximum Pulling Tension | ||
14.1 | Of Conductor | kN | 10.5 |
15 | Continuous current rating under the specified installation and operating conditions. Conductor temperature 90° C . Ground temperature 25° C and depth of laying 1000 mm | ||
16 | Short circuit capacity of conductor for 1/2/3 second assuming conductor temperature of 90 ° C prior to short circuit and 250 ° C during short circuit | ||
16.1 | 1.0 Secs | kA | 7.5 |
16.2 | 2.0 Secs | kA | 5.4 |
16.3 | 3.0 Secs | kA | 4.3 |
17 | TEST | ||
17.1 | Maximum D.C. resistance of conductor per km. at 20 degree C. | Ohm | 0.387 |
17.2 | Maximum A.C. resistance of conductor per km. at 90 degree C. | Ohm | 0.495 |
17.3 | A.C. Enduring Test voltage 2.5U0/ hours | kV/mim | 3.5/1 |
18 | Approximate drum dimension (dia & width) | mm/mm | 1600*1100 |
19 | Maximum length of cable in a drum (Metres) | m | 1020 |
20 | Minimum length of cable in a drum (Metres) | m | 1000 |
21 | Approximate gross weight of cable in a drum | TON | 2.3 |
22 | Expected Cable life. | Year | 30 |
Dibujo de configuración
Cu / XLPE / PVC 0.6 / 1 kV 4 × 50mm2
Construction |
Thickness(mm) |
Diameter(mm) |
1 --- Copper Conductor |
|
8.3(+0.1,-0.1) |
3 --- XLPE insulation |
1.0 |
10.3(+0.5,-0.5) |
3 --- PP filler |
|
24.9 |
4 --- Non-woven fabrics tape |
0.2 |
25.7 |
5--- PVC outer sheath |
1.9 |
29.5(+2.0,-2.0) |
Equipos avanzados de fabricación
Equipos de prueba avanzados
La compañía presentó el equipo de prueba y producción de alambres y cables de nivel avanzado del mundo, como el analizador de espectro DV-6E, el probador de impurezas en micro poros en línea, etc.
Advanced Testing Equipment Guarantee Producción de alta calidad
PRODUCTOS POR GRUPO : Cable de alimentación de baja tensión