Huayuan Gaoke Cable Co.,Ltd.
Cable de alimentación del aislamiento del PVC del conductor de cobre,Cobre Tape Screen PVC Filler Cover the Cable,Recubrimiento exterior de PVC de cinta de acero galvanizado para cable
Tipo de Pago: | L/C,T/T,D/P,Western Union |
---|---|
Incoterm: | FOB,CFR,CIF,FCA,CPT |
Cantidad de pedido mínima: | 500 Meter |
Modelo: YJV
Marca: HUAYUAN YONGTONG
Paquete: Tambores
productividad: 100KM/M
transporte: Ocean,Land,Air
Lugar de origen: BEIJING, CHINA
Apoyo sobre: 100KM/M
Certificados : CE,CCC,ISO
HS-Code: 8544601200
Hafen: Tianjin Port,Shanghai Port,Qingdao Port
Tipo de Pago: L/C,T/T,D/P,Western Union
Incoterm: FOB,CFR,CIF,FCA,CPT
HOJA DE DATOS TECHNICLA PARA CABLE DE ALIMENTACIÓN DE 6 kV 3C 120 SQmm
NO. | ITEM | UNIT | DATA |
1 | Name of Manufacturer: | Beijing Huayuan Gaoke | |
Cable Co.,Ltd. | |||
1.2 | Country of Manufacturer: | China | |
2 | Which type of manufacturing process viz. Continuous Catanery Vulcanisation (CCV) or vertical Catanery Vulcanisation system (VCV) or horizontal MDCV will be used to ensure circularity and concentricity of the extruded layers around the conductor. | CCV | |
3 | Type of Cable: | Cu/PVC/CTS/PVC/STA.PVC | |
4 | Rated nominal voltage | kV | 3.6/6 |
5 | Rated Maximum voltage | kV | 7.2 |
6 | Nominal cross-sectional area of Conductor | Sq.mm | 120 |
7 | Conductor | ||
7.1 | Material | Copper | |
7.2 | Shape & formation | Round | |
7.3 | Diameter of conductor | mm | 13 |
7.4 | Dia.Of Single Wire/Number of strands | mm | 2.87/19 |
8 | Insulation | ||
8.1 | Material | PVC | |
8.2 | Insulation Thickness(Min.Avg.) | mm | 3.4 |
8.3 | Diameter of Insulation(Approx.) | mm | 19.8 |
10 | Metallic Screen: | ||
10.1 | Material | Plain Annealed Copper Tape | |
10.2 | Thickness of the copper tape screen | mm | 0.1 |
10.3 | Diameter of the cable across the metallic screen(Approx.) | mm | 20.1 |
12 | Filler | ||
12.1 | Material | Extrusion PVC | |
12.2 | Diameter of Laid-Up Core | 44.9 | |
13 | Armouring | ||
13.1 | Material | galvanized steel tape | |
13.2 | Approximate thickness/layer | mm/ | 0.5/2 |
13.3 | Diameter of armouring (Approx.) | mm | 46.9 |
14 | Outer Sheath | ||
14.1 | Material | PVC | |
14.2 | Outer Sheath Thickness(Nominal) | 2.6 | |
14.3 | Over Diameter(Approx.) | 52.1 | |
15 | Conductor Weight | kg/km | 3141 |
15.1 | Total Cable Weight (Approx.) | kg/km | 6210 |
16 | Minimum Bending Radius | ||
16.1 | During Installation | mm | 650 |
16.2 | Installed | mm | 800 |
17 | Maximum Pulling Tension | ||
17.1 | Of Conductor | kN | 25.2 |
18 | Continuous current rating under the specified installation and operating conditions. Conductor temperature 90° C . Ground temperature 35° C and depth of laying 1500 mm | ||
18.1 | In Air | Amp | 312 |
18.2 | In Ground | Amp | 237 |
18.3 | In pipeline | Amp | 205 |
19 | Maximum value of electric stresses at the conductor screen (Calculation to be shown separately) | kV/mm | 1.32 |
19.1 | Maximum value of dielectric stress at the insulation | kV/mm | 0.86 |
20 | Short circuit capacity of conductor for 1/2/3 second assuming conductor temperature of 90 ° C prior to short circuit and 140 ° C during short circuit | ||
20.1 | 1.0 Secs | kA | 11.5 |
20.2 | 2.0 Secs | kA | 8.2 |
20.3 | 3.0 Secs | kA | 6.7 |
21 | Short circuit capacity of metallic screen for 1/2/3 second at screen temperature of 80 ° C prior to short circuit and 120 ° C during short circuit | ||
21.1 | 1.0 Secs | kA | 2.6 |
21.2 | 2.0 Secs | kA | 1.9 |
21.3 | 3.0 Secs | kA | 1.5 |
22 | Screen voltage under maximum operating conditions assuming all circuits connected | kV per km | 0.05 |
23 | TEST | ||
23.1 | Maximum D.C. resistance of conductor per km. at 20 degree C. | Ohm | 0.153 |
23.2 | Maximum A.C. resistance of conductor per km. at 80 degree C. | Ohm | 0.191 |
23.3 | Maximum electrostatic capacitance per km. of cable. | μF | 0.913 |
23.4 | Partial discharge at 1.50 Uo | pc | ≤ 10 |
23.5 | A.C. Enduring Test voltage 2.5U0/ hours | kV/mim | 12.5/5 |
23.6 | D.C.Out sheath Enduring Test voltage | kV/mim | 5kV/1min |
23.7 | Impulse test voltage | kV | 60 |
24 | Approximate drum dimension (dia & width) | mm/mm | 2000*1400 |
25 | Maximum length of cable in a drum (Metres) | m | 550 |
26 | Minimum length of cable in a drum (Metres) | m | 500 |
27 | Approximate gross weight of cable in a drum | TON | 3.3 |
28 | Expected Cable life. | Year | 30 |
Dibujo de configuración
Cu / LPE / AWA / PVC 6.35 / 11 (12) kV 3 × 95 mm 2
Construction |
Thickness(mm) |
Diameter(mm) |
1 --- Copper Conductor |
|
13.0(+0.1,-0.1) |
2 --- PVC insulation |
3.4 |
19.8(+0.5,-0.5) |
3 --- Copper tape screen |
0.1 |
20.1 |
4 --- PVC filler |
|
44.9 |
5 --- Galvanized steel tape |
0.5 |
46.9 |
6--- PVC outer sheath |
2.6 |
52.1(+2.0,-2.0) |
Equipos avanzados de fabricación
Equipos de prueba avanzados
La compañía presentó el equipo de prueba y producción de alambres y cables de nivel avanzado del mundo, como el analizador de espectro DV-6E, el probador de impurezas en micro poros en línea, etc.
Advanced Testing Equipment Guarantee Producción de alta calidad
1. Cable de alimentación de voltaje medio 2. Conductor de cobre de tres núcleos 3. Conductor de cobre de cinco núcleos Cable de 4.Mv Xlpe Cable blindado de 5.Copper Cable de núcleo único de 5.Pvc
PRODUCTOS POR GRUPO : Cable de alimentación de voltaje medio