FICHA TÉCNICA TECHNICLA PARA CABLE DE ALIMENTACIÓN 24 kV 3C 95 SQmm
NO. | ITEM | UNIT | DATA |
1 | Name of Manufacturer: | Beijing Huayuan Gaoke | |
Cable Co.,Ltd. | |||
1.2 | Country of Manufacturer: | China | |
2 | Which type of manufacturing process viz. Continuous Catanery Vulcanisation (CCV) or vertical Catanery Vulcanisation system (VCV) or horizontal MDCV will be used to ensure circularity and concentricity of the extruded layers around the conductor. | CCV | |
3 | Type of Cable: | AL/XLPE/PE | |
4 | Rated nominal voltage | kV | 12/20 |
5 | Rated Maximum voltage | kV | 24 |
6 | Nominal cross-sectional area of Conductor | Sq.mm | 95 |
7 | Conductor | ||
7.1 | Material | Aluminum | |
7.2 | Shape & formation | Round | |
7.3 | Diameter of conductor | mm | 11.2 |
7.4 | Dia.Of Single Wire/Number of strands | mm | 2.56/19 |
8 | Conductor Screen | ||
8.1 | Material | semi conductive material | |
8.2 | Thickness of semi-conductor screen | mm | 0.6 |
8.3 | Diameter of Semi-conductor(Approx.) | mm | 12.4 |
9 | Insulation | ||
9.1 | Material | XLPE | |
9.2 | Insulation Thickness(Min.Avg.) | mm | 5.5 |
9.3 | Diameter of Insulation(Approx.) | mm | 23.4 |
10 | Insulation Screen | ||
10.1 | Material | Semi-conductive material | |
10.2 | Insulation Screen Thickness(Approx.) | mm | 0.8 |
10.3 | Diameter of Insulation screen (Approx.) | mm | 25 |
11 | Metallic Screen: | ||
11.1 | Material | Aluminum wire | |
11.2 | Diameter of the Aluminum screen | mm | 2.83 |
12 | Filler | ||
12.1 | Material | Semi-conductive filler | |
12.2 | Diameter of Laid-Up Core | 54 | |
13 | Longitudinal water tightness | ||
13.1 | Material | Waterproof rope | |
13.2 | Approximate t diameter | mm | 3 |
14 | Cross sectional water tightness | ||
14.1 | Material | PE laminated AL type | |
14.2 | Thickness(Nominal) | 0.2 | |
14.3 | Diameter over the cross sectional water tightness layer (Approx.) | 55.2 | |
15 | Outer sheath | ||
15.1 | Material | PE | |
15.2 | Outer Sheath Thickness(Nominal) | mm | 3 |
15.3 | Over Diameter(Approx.) | mm | 61.2 |
16 | Conductor Weight | kg/km | 756 |
17 | Total Cable Weight (Approx.) | kg/km | 3210 |
18 | Minimum Bending Radius | ||
18.1 | During Installation | mm | 700 |
18.2 | Installed | mm | 500 |
19 | Maximum Pulling Tension | ||
19.1 | Of Conductor | kN | 11.4 |
20 | Continuous current rating under the specified installation and operating conditions. Conductor temperature 90° C . Ground temperature 35° C and depth of laying 1500 mm | ||
20.1 | In Air | Amp | 203 |
20.2 | In Ground | Amp | 147 |
20.3 | In pipeline | Amp | 128 |
21 | Maximum value of electric stresses at the conductor screen (Calculation to be shown separately) | kV/mm | 3.05 |
21.1 | Maximum value of dielectric stress at the insulation | kV/mm | 1.62 |
22 | Short circuit capacity of conductor for 1/2/3 second assuming conductor temperature of 90 ° C prior to short circuit and 200 ° C during short circuit | ||
22.1 | 1.0 Secs | kA | 9.6 |
22.2 | 2.0 Secs | kA | 6.9 |
22.3 | 3.0 Secs | kA | 5.8 |
23 | Short circuit capacity of metallic screen for 1/2/3 second at screen temperature of 80 ° C prior to short circuit and 200 ° C during short circuit | ||
23.1 | 1.0 Secs | kA | 2 |
23.2 | 2.0 Secs | kA | 1.5 |
23.3 | 3.0 Secs | kA | 1.2 |
24 | Screen voltage under maximum operating conditions assuming all circuits connected | kV per km | 0.05 |
25 | TEST | ||
25.1 | Maximum D.C. resistance of conductor per km. at 20 degree C. | Ohm | 0.32 |
25.2 | Maximum A.C. resistance of conductor per km. at 90 degree C. | Ohm | 0.41 |
25.3 | Maximum electrostatic capacitance per km. of cable. | μF | 0.302 |
25.4 | Partial discharge at 1.50 Uo | pc | ≤ 10 |
25.5 | A.C. Enduring Test voltage 3.5U0/ min | kV/mim | May-42 |
25.6 | D.C.Out sheath Enduring Test voltage | kV/mim | 5kV/1min |
25.7 | Impulse test voltage | kV | 120 |
26 | Approximate drum dimension (dia & width) | mm/mm | 2500*1400 |
27 | Maximum length of cable in a drum (Metres) | m | 600 |
28 | Minimum length of cable in a drum (Metres) | m | 500 |
39 | Approximate gross weight of cable in a drum | TON | 2000 |
30 | Expected Cable life. | Year | 30 |
Tamaño del cable y estructura de las secciones
AL / XLPE / PE 12/20 (24) kV 3 × 95 / 25AL mm 2
Construction |
Thickness(mm) |
Diameter(mm) |
1 --- ALuminum Conductor |
|
11.2(+0.1,-0.1) |
2 --- Conductor screen |
0.6 |
12.4 |
3 --- XLPE insulation |
5.5 |
23.4(+0.5,-0.5) |
4 --- Insulation screen |
0.8 |
25.0 |
5 --- Aluminum wire screen |
2.83 |
|
6 --- Semi-conducive filler |
|
54.0 |
7 --- Longitudinal water tightness |
3.0 |
|
8 --- PE laminated AL type |
0.2 |
55.2(+1.5,-1.5) |
9--- PE outer sheath |
3.0 |
61.2(+2.0,-2.0) |
Equipos avanzados de fabricación
Equipos de prueba avanzados
La compañía presentó el equipo de prueba y producción de alambres y cables de nivel avanzado del mundo, como el analizador de espectro DV-6E, el probador de impurezas en micro poros en línea, etc.
Advanced Testing Equipment Guarantee Producción de alta calidad
1. Cable coaxial de aluminio 2. Condcutor de aleación de aluminio XLPE 3. Conductor de aluminio de cuatro núcleos 4. Cable de revestimiento de aleación de aluminio 5. Aleación de aluminio de alta calidad 6. Conductor de aluminio de tres núcleos 7. Cable blindado con alambre de cobre
PRODUCTOS POR GRUPO : Cable aéreo