HOJA DE DATOS TECHNICLA PARA CABLE DE ALIMENTACIÓN DE 36 kV 1C 400 SQmm
NO. | ITEM | UNIT | DATA |
1 | Name of Manufacturer: |
|
Beijing Huayuan Gaoke |
Cable Co.,Ltd. | |||
2 | Country of Manufacturer: |
|
China |
3 | Which type of manufacturing process viz. Continuous Catanery Vulcanisation (CCV) or vertical Catanery Vulcanisation system (VCV) or horizontal MDCV will be used to ensure circularity and concentricity of the extruded layers around the conductor. |
|
CCV |
4 | Type of Cable: |
|
Cu/XLPE/SWA/PVC |
5 | Rated nominal voltage | kV | 18/30 |
6 | Rated Maximum voltage | kV | 36 |
7 | Nominal cross-sectional area of Conductor | Sq.mm | 400 |
8 | Conductor | ||
8.1 | Material |
|
Copper |
8.2 | Shape & formation |
|
Round |
8.3 | Diameter of conductor | mm | 23.8 |
8.4 | Dia.Of Single Wire/Number of strands | mm | 2.98/60 |
9 | Conductor Screen |
|
|
9.1 | Material |
|
semi conductive XLPE |
9.2 | Thickness of semi-conductor screen | mm | 0.8 |
9.3 | Diameter of Semi-conductor(Approx.) | mm | 25.4 |
10 | Insulation |
|
|
10.1 | Material |
|
XLPE |
10.2 | Insulation Thickness(Min.Avg.) | mm | 8.0 |
10.3 | Diameter of Insulation(Approx.) | mm | 41.4 |
11 | Insulation Screen |
|
|
11.1 | Material |
|
Semi-conductive material |
11.2 | Insulation Screen Thickness(Approx.) | mm | 0.8 |
11.3 | Diameter of Sime-Insulation(Approx.) | mm | 43.0 |
12 | Metallic Screen: | ||
12.1 | Material |
|
Copper tape |
12.2 | Thickness of the copper tape screen | mm | 0.12 |
12.3 | Diameter of the cable across the metallic screen(Approx.) | mm | 43.4 |
13 | Inner sheath |
|
|
13.1 | Material |
|
PVC |
13.2 | Approximate thickness | mm | 1.5 |
13.3 | Diameter of inner sheath (Approx.) | mm | 46.4 |
14 | Armouring |
|
|
14.1 | Material |
|
Aluminum wire+ nonmagnetic steel tape |
14.2 | Approximate diameter / thickness | mm/mm | 3.15/0.3 |
14.3 | Diameter of armouring (Approx.) | mm | 53.3 |
15 | Outer Sheath | ||
15.1 | Material |
|
PVC |
15.2 | Outer Sheath Thickness(Nominal) |
|
3.4 |
15.3 | Over Diameter(Approx.) |
|
60.1 |
16 | Conductor Weight | kg/km | 3542 |
16.1 | Total Cable Weight (Approx.) | kg/km | 7218 |
17 | Minimum Bending Radius |
|
|
17.1 | During Installation | mm | 1200 |
17.2 | Installed | mm | 900 |
18 | Maximum Pulling Tension |
|
|
18.1 | Of Conductor | kN | 28.0 |
19 | Continuous current rating under the specified installation and operating conditions. Conductor temperature 90° C . Ground temperature 35° C and depth of laying 1500 mm |
|
|
19.1 | In Air | Amp | 612 |
19.2 | In Ground | Amp | 418 |
19.3 | In pipeline | Amp | 396 |
20 | Maximum value of electric stresses at the conductor screen (Calculation to be shown separately) | kV/mm | 2.90 |
21 | Maximum value of dielectric stress at the insulation | kV/mm | 1.78 |
22 | Short circuit capacity of conductor for 1/2/3 second assuming conductor temperature of 90 ° C prior to short circuit and 250 ° C during short circuit |
|
|
22.1 | 1.0 Secs | kA | 51.6 |
22.2 | 2.0 Secs | kA | 36.6 |
22.3 | 3.0 Secs | kA | 30.0 |
23 | Short circuit capacity of metallic screen for 1/2/3 second at screen temperature of 80 ° C prior to short circuit and 200 ° C during short circuit |
|
|
23.1 | 1.0 Secs | kA | 2.3 |
23.2 | 2.0 Secs | kA | 1.5 |
23.3 | 3.0 Secs | kA | 1.3 |
24 | Screen voltage under maximum operating conditions assuming all circuits connected | kV per km | 0.05 |
25 | TEST |
|
|
25.1 | Maximum D.C. resistance of conductor per km. at 20 degree C. | Ohm | 0.0470 |
25.2 | Maximum A.C. resistance of conductor per km. at 90 degree C. | Ohm | 0.0614 |
25.3 | Maximum electrostatic capacitance per km. of cable. | μF | 0.262 |
25.4 | Partial discharge at 1.50 Uo | pc | ≤ 10 |
25.5 | A.C. Enduring Test voltage 2.5U0/ hours | kV/mim | 63/3 Not breakdown |
25.6 | D.C.Out sheath Enduring Test voltage | kV/mim | 5kV/1min |
25.7 | Impulse test voltage | kV | 120 |
26 | Approximate drum dimension (dia & width) | mm/mm | 2200*1400 |
27 | Maximum length of cable in a drum (Metres) | m | 510 |
28 | Minimum length of cable in a drum (Metres) | m | 500 |
39 | Approximate gross weight of cable in a drum | TON | 3.9 |
30 | Expected Cable life. | Year | 30 |
Cu / LPE / SWA / PVC 18/30 (36) kV 1 × 400 mm 2
Construction |
Thickness(mm) |
Diameter(mm) |
1 --- Copper Conductor |
|
23.8(+0.1,-0.1) |
2 --- Conductor screen |
0.8 |
25.4 |
3 --- XLPE insulation |
8.0 |
41.4(+0.5,-0.5) |
4 --- Insulation screen |
0.8 |
43.0 |
5 --- Copper tape screen |
0.12 |
43.4 |
6 --- PVC inner sheath |
1.5 |
46.4(+1.5,-1.5) |
7 --- Aluminum wire armor+steel tape |
3.15+0.3 |
53.3 |
8 --- PVC outer sheath |
3.4 |
60.1(+2.5,-2.0) |
Equipos avanzados de fabricación
Equipos de prueba avanzados
La compañía presentó el equipo de prueba y producción de alambres y cables de nivel avanzado del mundo, como el analizador de espectro DV-6E, el probador de impurezas en micro poros en línea, etc.
Advanced Testing Equipment Guarantee Producción de alta calidad
1.33kv Cable 2. Cable de alimentación de voltaje medio 3. Cable de incendio de incendio 4. Cable de humo bajo 5. Cables de cable eléctrico 6. Cable blindado de cable de cobre
PRODUCTOS POR GRUPO : Cable de alimentación de voltaje medio